Terminal Unit Forano BS
CONCEALED / HOLLOW WALL INSTALLATION
The unit is used to withdraw compressed gases and vacuum from a central medical gas supply system in accordance with EN ISO 7396–1; integration of plugs and medical appliances with plug-in connections in line with BS 5682. The Forano terminal unit complies with the requirements of ENISO 9170–1.
Advantages
- Two-part construction: gas-specific basic block and connector mounting
- Sophisticated design: all-metal actuator with laser labelling, front panel with wavy lines and diaphragm ring
- Easy installation and servicing: cartridge with sealing elements, replacement possible without blocking the station
- Unique marking: gas-type labelling – print labelling: chemical symbol + English + CE, colour coding: neutral or in line with DIN EN ISO 5359.
- TECHNICAL DATA
Input: 8 mm copper pipe Operation pressure: 400 kPa bis 500 kPa (overpressure) – compressed gases
< 60 kPa (absolute pressure) – vacuum - Order numbers
Forano, O2, concealed / hollow wall installation, type DIN / AGA / NF 903.250 Forano, AIR, concealed / hollow wall installation, type DIN / AGA / NF 903.251 Forano, VAC, concealed / hollow wall installation, type DIN / AGA / NF 903.252 Forano, N2O, concealed / hollow wall installation, type DIN / AGA / NF 903.253 Forano, CO2, concealed / hollow wall installation, type DIN / AGA / NF 903.255 Forano, special gas, concealed / hollow wall installation, type DIN / AGA / NF 903.25
All front parts for terminal unit Forano DIN, neutral or DIN EN ISO 5359 colour coding, can be found here. - ACCESSORIES
Front / wave screen to cover the built-in variant UP/HW 903.258 Front / wave screen to cover the built-in variant UP/HW (sales unit = 6 pcs.) UP/HW (sales unit = 6 pcs.) 903.259